Governor Model: IEEEG1, IEEEG1D and IEEEG1_GE
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < T3 < Mult*TimeStep then T3 = Mult*TimeStep
- If 0.0 < T4 < 0.5*Mult*TimeStep then T4 = 0, ElseIf 0.5*Mult*TimeStep < T4 < Mult*TimeStep then T4 = Mult*TimeStep
- If 0.0 < T5 < 0.5*Mult*TimeStep then T5 = 0, ElseIf 0.5*Mult*TimeStep < T5 < Mult*TimeStep then T5 = Mult*TimeStep
- If 0.0 < T6 < 0.5*Mult*TimeStep then T6 = 0, ElseIf 0.5*Mult*TimeStep < T6 < Mult*TimeStep then T6 = Mult*TimeStep
- If 0.0 < T7 < 0.5*Mult*TimeStep then T7 = 0, ElseIf 0.5*Mult*TimeStep < T7 < Mult*TimeStep then T7 = Mult*TimeStep
- If Uo < Uc then swap the values. If Uo < 0 then Uo change sign to positive. If Uc > 0 then change sign to negative.
- If Pmax < Pmin then swap the values.
- K1 to K8: Check K1+K3+K5+K7 and K2+K4+K6+K8 <= 1.0 and if not normalized values to 1.0.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Pmech > Pmax , then Pmax = Pmech or if Pmech < Pmin , then Pmin = Pmech
Model Equations and/or Block Diagrams
Parameters for IEEEG1:
| K | Governor gain (recirpocal of droop), pu |
| T1 | Governor lag time constant, sec |
| T2 | governor lead time constant, sec |
| T3 | Valve positioner time constant, sec |
| Uo | Maximum valve opening velocity, pu/sec |
| Uc | Maximum valve closing velocity, pu/sec |
| Pmax | Maximum valve opening, pu of mwcap |
| Pmin | Minimum valve opening, pu of mwcap |
| T4 | High pressure turbine bowl time constant, sec |
| K1 | Fraction of hp shaft power after first boiler pass |
| K2 | Fraction of lp shaft power after first boiler pass |
| T5 | Reheater time constant, sec |
| K3 | Fraction of hp shaft power after second boiler pass |
| K4 | Fraction of lp shaft power after second boiler pass |
| T6 | Crossover time constant, sec |
| K5 | Fraction of hp shaft power after third boiler pass |
| K6 | Fraction of lp shaft power after third boiler pass |
| T7 | Double reheat time constant, sec |
| K7 | Fraction of hp shaft power after fourth boiler pass |
| K8 | Fraction of lp shaft power after fourth boiler pass |
| db1 | Intentional deadband width, Hz |
| Eps | Intentional db hysteresis, Hz |
| db2 | Unintentional deadband, MW |
| Gv1 | Nonlinear gain point 1, pu gv |
| Pgv1 | Nonlinear gain point 1, pu power |
| Gv2 | Nonlinear gain point 2, pu gv |
| Pgv2 | Nonlinear gain point 2, pu power |
| Gv3 | Nonlinear gain point 3, pu gv |
| Pgv3 | Nonlinear gain point 3, pu power |
| Gv4 | Nonlinear gain point 4, pu gv |
| Pgv4 | Nonlinear gain point 4, pu power |
| Gv5 | Nonlinear gain point 5, pu gv |
| Pgv5 | Nonlinear gain point 5, pu power |
| Gv6 | Nonlinear gain point 6, pu gv |
| Pgv6 | Nonlinear gain point 6, pu power |
| Trate | Turbine rating, MW |
Parameters for IEEEG1D:
| K | Governor gain (recirpocal of droop), pu |
| T1 | Governor lag time constant, sec |
| T2 | governor lead time constant, sec |
| T3 | Valve positioner time constant, sec |
| Uo | Maximum valve opening velocity, pu/sec |
| Uc | Maximum valve closing velocity, pu/sec |
| Pmax | Maximum valve opening, pu of mwcap |
| Pmin | Minimum valve opening, pu of mwcap |
| T4 | High pressure turbine bowl time constant, sec |
| K1 | Fraction of hp shaft power after first boiler pass |
| K2 | Fraction of lp shaft power after first boiler pass |
| T5 | Reheater time constant, sec |
| K3 | Fraction of hp shaft power after second boiler pass |
| K4 | Fraction of lp shaft power after second boiler pass |
| T6 | Crossover time constant, sec |
| K5 | Fraction of hp shaft power after third boiler pass |
| K6 | Fraction of lp shaft power after third boiler pass |
| T7 | Double reheat time constant, sec |
| K7 | Fraction of hp shaft power after fourth boiler pass |
| K8 | Fraction of lp shaft power after fourth boiler pass |
| dbH | Deadband High (pu) |
| dbL | Deadband Low (pu) |
| Trate | Turbine rating, MW |
Parameters for IEEEG1_GE:
| Trate | Turbine rating, MW |
| K | Governor gain (recirpocal of droop), pu |
| T1 | Governor lag time constant, sec |
| T2 | governor lead time constant, sec |
| T3 | Valve positioner time constant, sec |
| Uo | Maximum valve opening velocity, pu/sec |
| Uc | Maximum valve closing velocity, pu/sec |
| Pmax | Maximum valve opening, pu of mwcap |
| Pmin | Minimum valve opening, pu of mwcap |
| T4 | High pressure turbine bowl time constant, sec |
| K1 | Fraction of hp shaft power after first boiler pass |
| K2 | Fraction of lp shaft power after first boiler pass |
| T5 | Reheater time constant, sec |
| K3 | Fraction of hp shaft power after second boiler pass |
| K4 | Fraction of lp shaft power after second boiler pass |
| T6 | Crossover time constant, sec |
| K5 | Fraction of hp shaft power after third boiler pass |
| K6 | Fraction of lp shaft power after third boiler pass |
| T7 | Double reheat time constant, sec |
| K7 | Fraction of hp shaft power after fourth boiler pass |
| K8 | Fraction of lp shaft power after fourth boiler pass |
| db1 | Intentional deadband width, Hz |
| Eps | Intentional db hysteresis, Hz |
| db2 | Unintentional deadband, MW |
| Gv1 | Nonlinear gain point 1, pu gv |
| Pgv1 | Nonlinear gain point 1, pu power |
| Gv2 | Nonlinear gain point 2, pu gv |
| Pgv2 | Nonlinear gain point 2, pu power |
| Gv3 | Nonlinear gain point 3, pu gv |
| Pgv3 | Nonlinear gain point 3, pu power |
| Gv4 | Nonlinear gain point 4, pu gv |
| Pgv4 | Nonlinear gain point 4, pu power |
| Gv5 | Nonlinear gain point 5, pu gv |
| Pgv5 | Nonlinear gain point 5, pu power |
| Gv6 | Nonlinear gain point 6, pu gv |
| Pgv6 | Nonlinear gain point 6, pu power |